Circuit Breaker Compact NSX160F

Circuit Breaker Compact NSX160F

Circuit breaker Compact NSX160F, 36 KA at 415 VAC, TMD trip unit 160 A, 3 poles 3d

Finally, for more information Click here.

Get a QUOTE today

Circuit breaker Compact NSX160F, 36 KA at 415 VAC, TMD trip unit 160 A, 3 poles 3d

Finally, for more information Click here.

Get a QUOTE today

 

Short Code

Product or Component Type

Circuit breaker

Device Application

Distribution

Poles Description

3P

Protected Poles Description

3t

Network Type

AC

Network Frequency

50/60 Hz

[In] Rated Current

160 A at 40 °C

[Ui] Rated Insulation Voltage

800 V AC 50/60 Hz

[Uimp] Rated Impulse withstand Voltage

8 kV

[Ue] Rated Operational Voltage

690 V AC 50/60 Hz

Breaking Capacity Code

F 36 kA 415 V AC

Breaking Capacity

10 kA at 600 V AC 50/60 Hz conforming to UL 508
85 kA at 240 V AC 50/60 Hz conforming to UL 508
22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
35 kA at 480 V AC 50/60 Hz conforming to UL 508
30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2

[Ics] Rated Service Breaking Capacity

35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
22 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
8 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2

Suitability for Isolation

Yes conforming to EN 60947-2
Yes conforming to IEC 60947-2

Utilisation Category

Category A

Trip Unit Name

TM-D

Trip Unit Technology

Thermal-magnetic

Pollution Degree

3 conforming to IEC 60664-1