DRS-100-1P - Direct Connect 100A Single Phase Energy Meter

DRS-100-1P - Direct Connect 100A Single Phase Energy Meter

The DRS range of MID APPROVED, direct connected energy meters represents a
multi-function range of kWh meters in the Crompton Instruments portfolio.
The DRS-100-1P, energy meter is an accurate and cost effective solution for
measurement and display of importing and exporting energy parameters for single
phase networks. Its easy programming, mounting and user-friendly navigation make the
DRS-100-1P an ideal choice for customers who require reliable energy measurement.
The product features a DIN-rail enclosure and backlit LCD display.
The DRS-100-1P has two communication interfaces
• Modbus™ RTU protocol
• Two pulsed outputs

Features
• MID D certified
• Class B (kWh) to EC 2004/22/EC
• Direct connect to 100A
• DIN-rail enclosure DIN 43880
• Import / export kWh
• Modbus™ RTU protocol
• Two pulsed outputs
Benefits
• Cost effective
• Simple navigation
• Tamper-proof
Approvals
• IEC 50470-1
• IEC 50470-3
• IEC 62053-21
• IEC 62052-11
• IEC 61010-1
• IEC 60068

For more information on the DRS-100-1P – Direct Connect 100A Single Phase Energy Meter Click here.

Get a QUOTE today

 

The DRS range of MID APPROVED, direct connected energy meters represents a
multi-function range of kWh meters in the Crompton Instruments portfolio.
The DRS-100-1P, energy meter is an accurate and cost effective solution for
measurement and display of importing and exporting energy parameters for single
phase networks. Its easy programming, mounting and user-friendly navigation make the
DRS-100-1P an ideal choice for customers who require reliable energy measurement.
The product features a DIN-rail enclosure and backlit LCD display.
The DRS-100-1P has two communication interfaces
• Modbus™ RTU protocol
• Two pulsed outputs

Features
• MID D certified
• Class B (kWh) to EC 2004/22/EC
• Direct connect to 100A
• DIN-rail enclosure DIN 43880
• Import / export kWh
• Modbus™ RTU protocol
• Two pulsed outputs
Benefits
• Cost effective
• Simple navigation
• Tamper-proof
Approvals
• IEC 50470-1
• IEC 50470-3
• IEC 62053-21
• IEC 62052-11
• IEC 61010-1
• IEC 60068

For more information on the DRS-100-1P – Direct Connect 100A Single Phase Energy Meter Click here.

Get a QUOTE today

 

Short Code

Input - Nominal Input Voltage

63.5-276V AC L-N (173 – 500 V L-L)
600 V MAX

Input - Max. Continuous Input Overload Voltage

120% of nominal

Input - Max. Short Duration Input Voltage

2 x nominal voltage for 1 second

Input - Nominal Input Voltage Burden

< 0.2VA per phase

Input - Nominal Input Current

0.5-10 (100A)

Input - Nominal Input Current Burden

< 0.5 VA

Input - Max. Continuous Input Overload Current

120% of nominal

Input - Max. Short Duration Input Current

20 x nominal current for (10 msec)

Auxiliary - Operating Range

Self powered

Auxiliary - Supply Burden

< 10 VA

Accuracy - Voltage (V)

+/- 0.5% of range maximum

Accuracy - Current (A)

+/- 0.5% of range maximum

Accuracy - Frequency (Hz)

+/- 0.2% of mid-frequency

Accuracy - Power Factor (PF)

+/- 1% of unity (0.01)

Accuracy - Active Power (W)

+/- 1.0% of range maximum

Accuracy - Reactive Power (VAr)

+/- 1.0% of range maximum

Accuracy - Apparent Power (VA)

+/- 1.0% of range maximum

Accuracy - Active Energy (kWh)

+/- 1.0% of range maximum to IEC 62053-21

Accuracy - Reactive Energy (kVarh)

+/- 1.0% of range maximum to IEC 62053-24

Accuracy - Response Time

1 sec, typical, to >99% of final reading at
50Hz

Measured Range - Voltage (V)

5 – 120% of nominal (Min 100V – self powered)

Measured Range - Current (A)

5 – 120% of nominal

Measured Range - Frequency (Hz)

44 – 66 Hz +/- 2%

Measured Range - Power (W, VAr, VA)

5 – 144% of nominal (bi-directional)

Measured Range - Energy

7 digit, upto 999999.9 kWh / kVArh

Measured Range - Power Factor

4 quadrant

Measured Range - Input Waveform

Sinusoidal (distortion factor < 0.05)

Environment - Operating Temperature

-25˚C to +55˚C

Environment - Storage Temperature

-40˚C to +70˚C

Environment - Relative Humidity

0 to 95%, non-condensing

Environment - Shock

30g in 3 planes

Environment - Vibration

10Hz to 50Hz, IEC 60068-2-6, 2g

Environment - Dielectric Voltage

4kV

Environment - Altitude

3000m

Environment - Warm-up

1 minute

Environment - Magnetic Field of External Origin

Terrestrial flux

Outputs - Pulsed Output Relay (Configurable)

Opto-coupled, potential-free SPST-NO
contact

Outputs - Contact Rating Current

2-27mA at 27V DC

Outputs - Contact Rating Voltage

5-27V DC

Outputs - Pulse Width

60 / 100 / 200 ms

Outputs - Pulse Rate

0.01 / 0.1 / 1 / 10 / 100 kWh / kVArh
Default. 1 pulse per Wh/VArh

Outputs - Pulsed Output Relay (Non-Configurable)

1000 Imp/kWh

Outputs - Communications

Modbus RTU (RS485)

Outputs - Type

2-wire half duplex

Outputs - Baud Rate

2400, 4800, 9600, 19.2 K, 38.4 K

Outputs - Address

1 to 247

Outputs - Parity

None (default) / Odd / Even

Outputs - Stop Bits

1 (default) / 2

Enclosure - Enclosure Style

DIN-rail to DIN 43880

Enclosure - Dimensions

99x36x63mm (LxWxH)

Enclosure - Protection Rating

Front IP51

Enclosure - Material

Self extinguishing UL 94 V-O

Enclosure - Weight

216 g

Enclosure - Cable Size

2.5mm2 – 25mm2 stranded cable.
AWG 12 – 4