SC 200 2-channel Controller, 2x digital, 2x mA OUT

SC 200 2-channel Controller, 2x digital, 2x mA OUT

One controller for the broadest range of sensors
Digital 2-channel Controller with 2 digital Sensor Inputs and 2 x 0/4-20mA OUTPUTS.
The digital 2-channel controller is compatible with our complete range of over 40 digital and analogue sensors and determines 14 parameters.
All logged data can be extracted via SD Card slot.
One controller for 40+ sensors and 14 parameters
The digital 2 channel SC 200 Controller is compatible with our complete range of digital and analogue sensors. There are 40+ sensors to
choose – from Ammonium to Turbidity as well as special parameters such as oil in water. The one stop shop controller and its family of sensors
monitor processes for all applications in wastewater, drinking and process water. Standardisation on one controller reduces maintenance
complexity, time and costs. Plus you only have only one company to call.
Easy to extract data
To help you analyse and further improve your processes the SC 200 offers a new solution for simple data management. All logged measuring
and diagnosis data can be easily extracted in XML format from the controller via the SD Card slot.
Easy to keep firmware up to date
A new legal regulation is only one of several reasons why instrumentation firmware must always be kept up to date. Aside from legal
requirements we invest heavily to add new functionality, new parameters, new sensors etc. SC 200 makes this easy via the SD card slot.
One controller for all applications
Hach is the recognised leader for water analytical solutions. With the launch of the SC 200, more than 40 different analogue and digital plug
& play sensors can now be combined. Due to its rugged and robust metal enclosure, the SC 200 is suitable for industrial applications virtually
anywhere.
With the communication options PROFIBUS DP and MODBUS RS232/ RS485, the controller can be easily integrated into digital networks.
The modular concept (one slot for a communication card of choice and two slots for input cards) makes the SC 200 stand out in terms of
capability and flexibility.
Many additional versions available on request

£1,520.00

Firstly, SC 200 2-channel Controller with 2 digital Sensor Inputs and 2 x 0/4-20mA OUTPUTS.
The digital 2-channel controller is compatible with our complete range of over 40 digital and analogue sensors and determines 14 parameters.  As well as this, all logged data can be extracted via SD Card slot.

  • One controller for 40+ sensors and 14 parameters
  • Easy to extract data
  • Easy to keep firmware up to date
  • One controller for all applications
  • Many additional versions available on request

Finally, for more information about the Hach SC 200 2-channel Controller Click here.

Get a QUOTE today

Short Code

Analouge Output Functional Mode

Linear, logarithmic, bi-linear, PID

Analogue Outputs

Two (Five with optional expansion module) 0/4 to 20 mA isolated current outputs, max 550 Ω,
Accuracy:± 0.1% of FS (20mA) at 25 °C, ± 0.5% of FS over -20 °C to 60 °C range

Communication Digital

MODBUS RS232 / RS485, PROFIBUS DPV1 optional

Conduit Openings

1/2" NPT Conduit

Dimensions (H x W x D)

144 mm x 144 mm x 181 mm

Display

Graphic dot matrix LCD with LED backlighting

Display Resolution

240 x 160 pixels

Display Size

48 x 68 mm

Electrical Certifications

EMC – Certified CE compliant for conducted and radiated emissions (EN 50081-2) and immunity
(EN 61000-6-2);General purpose – UL through ETL;Class I, Div. 2 (Groups. A, B, C, and D) –
CSA (pending)

Enclosure Waterproof Rating

IP66 / NEMA 4X

Length

181mm

Manual Languages

Bulgarian, Chinese (PRC), Croatian, Czech, Danish, Dutch, English, Estonian, Finnish, French,
German, Greek, Hungarian, Italian, Japanese, Korean, Lithuanian, Polish, Portuguese (Brazil),
Portuguese (Portugal), Romanian, Russian, Slovak, Slovenian, Spanish, Swedish, Thai, Turkish

Material

Polycarbonate
Aluminium (powder coated)
Stainless steel

Mounting Configurations

Wall
Pole
Panel Mounting

Operating Temperature Range

-20 – 60 °C at 0 – 95% RH (non-condensing)

Power Requirements (Hz)

50 – 60 Hz

Power Requirements (Voltage)

100 – 240 V AC

Relay Functions

Alarm, Timer, Feeder Control, PWM or Fm Control, System Alarm

Relay Operational Mode

Primary or secondary measurement, calculated value (dual channel only) or timer

Relay

Four electromechanical SPDT (Form C) contacts, 1200 W, 5 A

Security Levels

2 password-protected levels

Sensor Input

Digital

Storage Conditions

-20 °C – 70 °C

Warranty

2 Years

Weight

1.7 kg