TeSys K Contactor - 3P(3 NO)

TeSys K Contactor - 3P(3 NO)

Range: TeSys
Product or component type: Contactor
Product name: TeSys K
Device short name: LC1K
Device application: Control
Contactor application: Motor control

Finally, for more information Click here.

Get a QUOTE today

Clear

Range: TeSys
Product or component type: Contactor
Product name: TeSys K
Device short name: LC1K
Device application: Control
Contactor application: Motor control

Finally, for more information Click here.

Get a QUOTE today

Short Code

, , , , ,

Pole Description

3P

Power Pole Contact Composition

3 NO

[Ue] Rated Operational Voltage

Power circuit: 690 V AC 50/60 Hz
Signalling circuit: <= 690 V AC 50/60 Hz

[Ie] Rated Operational Current

6 A at <= 440 V AC AC-3 for power circuit, 20 A (at <50 °C) at <= 440 V AC AC-1 for power circuit 9 A at <= 440 V AC AC-3 for power circuit 16 A (at <70 °C) at 690 V AC AC-1 for power circuit

[Uc] Control Circuit Voltage

230 V AC 50/60 Hz, -, 24 V AC 50/60 Hz, 110 V AC 50/60 Hz

Auxiliary Contact Composition

1 NO, 1 NC

[Uimp] Rated Impulse Withstand Voltage

8 kV

[Ith] Conventional Free Air Thermal Current

20 A (at 50 °C) for power circuit 10 A (at 50 °C) for signalling circuit

Rated Breaking Capacity

110 A at 415 V conforming to IEC 60947
110 A at 440 V conforming to IEC 60947
80 A at 500 V conforming to IEC 60947
110 A at 220…230 V conforming to IEC 60947
110 A at 380…400 V conforming to IEC 60947
70 A at 660…690 V conforming to IEC 60947

Average Impedance

3 mOhm – Ith 20 A 50 Hz for power circuit

[Ui] Rated Insulation Voltage

Power circuit: 600 V conforming to UL 508
Power circuit: 690 V conforming to IEC 60947-4-1
Signalling circuit: 690 V conforming to IEC 60947-4-1
Signalling circuit: 690 V conforming to IEC 60947-5-1
Signalling circuit: 600 V conforming to UL 508
Power circuit: 600 V conforming to CSA C22.2 No 14
Signalling circuit: 600 V conforming to CSA C22.2 No 14

Mounting Support

Plate
Rail

Tightening Torque

1.3 N.m – on screw clamp terminals – with screwdriver Philips No 2
1.3 N.m – on screw clamp terminals – with screwdriver flat Ø 6 mm

Non Overlap Distance

0.5 mm

Maximum Operating Rate

3600 cyc/h

Minimum Switching Current

5 mA for signalling circuit

Minimum Switching Voltage

17 V for signalling circuit